Aa3Evv - ICP DAS USA I-7021 User Manual

I-7000/7022/7024 series, m-7022/7024/7028 series
Table of Contents

Advertisement

I-7021, I-7021P, I-7022, I-7024, I-7024R
M-7022, M-7024, M-7024L, M-7024R, M-7024U, M-7028

2.38 ~AA3EVV

Description:
Enables/disables the host watchdog and sets the host
watchdog timeout value of a module.
Syntax:
~AA3EVV[CHKSUM](CR)
~
Delimiter character
AA
Address of the module to be set (00 to FF)
3
Command to set the host watchdog
E
1: enable the host watchdog
0: disable the host watchdog
VV
Two hexadecimal digits to represent the timeout
value in tenths of a second, for example, 01
denotes 0.1 seconds and FF denotes 25.5
seconds.
Response:
Valid command:
Invalid command: ?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
Address of the responding module (00 to FF)
There will be no response if the command syntax is
incorrect, there is a communication error, or there is no
module with the specified address.
I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
!AA[CHKSUM](CR)
127

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents