2.4 #AAN(Data)

Description:
Writes the data to a specified analog output channel.
Syntax:
#AAN(Data)[CHKSUM](CR)
#
Delimiter character
AA
Address of the module to be written (00 to FF)
N
The analog output channel to be written, zero
based.
(Data)
Data to be written to the analog output channel,
see Section 1.11 for the data format.
Response:
Valid Command:
Out of Range:
Ignored:
>
Delimiter character for a valid command
?
Delimiter character indicates that the data is out
of range. If it is over range, then the output will
be set to the maximum value of the range. If it
is under range, then the output will be set to the
minimum value of the range.
!
Delimiter character indicates that the command
is ignored, because the host watchdog timeout
occurs. The output is set to the safe value.
There will be no response if the command syntax is
incorrect, there is a communication error, or there is no
module with the specified address.
I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
>[CHKSUM](CR)
?[CHKSUM](CR)
![CHKSUM](CR)