Single EOL resistors allows the use
of N/C and/or Normally Open contacts.
C
5.6KΩ
Note: Option 2 must be set to OFF to enable these options.
Default - OFF
Option 4 - Test Once a Day Enabled/Disabled
Allows transmission test daily. Default - Disabled.
Option 5 - Test Once a Week Enabled/Disabled
Allows transmission test weekly.
Note: This option will be overridden If option 4 is set for daily test transmissions.
Default - Enabled.
Option 6 - Enrolled with Connect 24 /Not Enrolled
This option is set automatically during the enrollment procedure with
Connect 24. IF the Skyroute CL3050 is reset to the default settings this option
must be set to ON for the Skyroute CL3050 to resume communications.
Default - Not Enrolled.
Options 7, 8 - System Use
Caution:
Default - OFF.

[12] Skyroute CL3050 Configuration Options 2

Option 1 - Swinger Shutdown Enabled/Disabled
This option limits the number of alarm events transmitted per zone to 8 until the
counter has been reset (counter automatically resets at midnight), then event
transmissions will resume. Default - Enabled
Note:

[13] Skyroute CL3050 Trouble Output mask

The PGM output is dedicated for trouble indications. If a control panel is not
monitoring the Skyroute CL3050, an LED or a buzzer can be connected between
this terminal and the RED terminal for a trouble indication. The PGM terminal
switches low from an open-collector state. Connect to the control panel using a
single EOL resistor configuration.
Zx
C
Zx
C
Zx
5.6KΩ
5.6KΩ
Do NOT change these settings unless it is requested by DSC
technical support personnel.
Tampers and Faults will be counted unless they are disabled in
section [20].
6 Programming Descriptions
Double EOL resistors allows the
zone to be monitored for fault,
tamper, secure and violated condi-
tions. Only Normally Closed contacts
can be used in this configuration
C
Tamper
Contact
5.6KΩ
11
Z x
C
Z x
5.6KΩ
5.6KΩ
All Modes
All Modes
All Modes
All Modes
Modes 2, 3
All Modes
5.6KΩ