Skyroute CL3050 Standalone Wireless Communicator
[02]
Mode 2 - (2) 24-Hour Zones
In this mode, both the YEL and
GRN terminals on the Skyroute
CL3050 will be used as zone
inputs. These zones will support
the DSC standard EOL configura-
tion and loop response. Pro-
gramming sections will allow the
installer to change the default
zone types and attributes. The
Skyroute CL3050 will continu-
ously monitor these zones and transmit any alarms that occur to the central sta-
tion.
[03]
Mode 3 - (8) 24-Hour Zones
In this mode, the Skyroute
CL3050 is connected to a
PC5108 zone expander using
the corresponding RED, BLK,
YEL and GRN terminals. The
Skyroute CL3050 will drive the
Keybus to communicate with
the PC5108. A +12V
ply connected to the RED and
BLK terminals is required
when using this mode. The Programming sections will allow the installer to
change the default zone types and attributes. The Skyroute CL3050 will continu-
ously monitor these zones and transmit any alarms that occur to the central
station.
Note: This configuration can not be used with an AC supply.
Note: Jumpers on the PC5108 must be set as follows:
Default - [01 -03] dependant on start up configuration

[11] Skyroute CL3050 Configuration Options 1

Option 1 - A Channel Selected/ B Channel Selected.
This Option determines whether cellular channel "B" or channel "A" is used. In
Canada, Channel B is used (Default). In the USA refer to the SID list for the chan-
nel of the cellular service provider in your area. Default - Channel B
Option 2 - Normally Closed Loops/ End-of-line Resistors
Normally Closed Loops can be wired as shown. Multiple
Normally Closed contacts can be wired in series. For Double
or Single EOL resistors this option must be set to OFF.
Default - Normally Closed (N/C) Loops.
Option 3 - Double EOL Resistors/Single EOL Resistors
This option selects Double EOL resistors (ON) or Single EOL resistors (OFF) wired
as indicated
To Keybus
Connections
on PC5108
sup-
DC
J1
ON
J2
OFF
J3
ON
10
RED
Input Voltage
9-12V
or V
AC
DC
Zone 1 Input
Zone 2 Input
Zone Common
Trouble Output
RED
System Common
Trouble Output
J4
OFF
J5
OFF
J6
ON
BLK YEL GRN COM PGM
BLK YEL GRN COM PGM
All Modes
Mode 2, 3
Mode 2, 3