Ethernet/Cellular Programming Options - DSC 3G2080 Installation Manual

Cellular alarm communicator - international, internet and hspa dual-path alarm communicator
Hide thumbs Also See for 3G2080:
Table of Contents

Advertisement

Trouble indic-
Trouble
ation
Indicator Digit
Yellow LED
07
– 7 Flashes
Yellow LED
08
– 8 Flashes
Yellow LED -
09
9 Flashes
Yellow LED
0C
– 12 Flashes
All LEDs
flashing
N/A
together
Red and
Yellow LEDs
N/A
flashing
together
Only Green
LEDs
N/A
flashing
Green LEDs
N/A
alternating
The programming sections described in this document can be viewed at the keypad LCD. To start programming enter: [*] [8]
[installer code] [851] [section number] , where section number is the 3-digit section number referenced in this section. The
programming worksheets at the end of this document can be used to record the new values when programming changes have
been made from the default values.
Possible Causes
Receiver Not
Available
Receiver
Supervision
Trouble
FTC Trouble
Module
Configuration
Trouble
Boot Loader
Failed
Initialization
Sequence
Hardware Default
Jumper
Radio Reset or
Radio Initialization

Ethernet/Cellular Programming Options

Trouble Possible Solution
If problem persists, replace the Ethernet cable and RJ45 connector.
l
Ensure that the Ethernet path has Internet connectivity.
l
If using a static IP address, confirm that the gateway and subnet mask
l
are entered correctly.
If the network has a firewall, ensure the network has the programmed
l
outgoing ports open (default UDP port 3060 and port 3065).
Ensure that all the receivers are programmed for DHCP or have the
l
proper IP address and port number.
Ensure the cellular receiver APNs have been programmed with the
l
access point name provided by the cellular provider.
If Common Mode is used, and only one path is initialized while the
l
other path is not successful, generate a manual test transmission over
both paths or power cycle the communicator to recover the 'Receiver
Not Available' trouble.
This trouble is indicated when supervision is enabled and the unit is
l
not able to successfully communicate with the receiver.
If this trouble persists, contact the central station.
l
The unit has exhausted all communications attempts to all
l
programmed receivers for events generated by the communicator.
Restart the system, if trouble persists, contact the dealer.
l
This indication appears when section [021] system account code or
l
sections [101]; [111]; [201]; and [211] receiver account code have not
been programmed. Ensure that a valid account code has been
entered in these sections.
Disconnect power, then reconnect power to the communicator
l
module.
The unit is still initializing please wait while the unit gets its
l
programming and establishes a connection to all programmed
receivers.
NOTE: This process may take several minutes to complete.
The hardware default jumper is installed and must be removed. See
l
Figure 3.
If this status persists and the yellow LED shows 5 flashes, confirm that
l
the SIM card is active.
12