8.8. Kentix IO-Modules

The AlarmManager-PRO can be extended by additional digital Inputs and Outputs via special Expansion
modules. For this 2 external modules (KIO7052 with 8 digital Inputs / Outputs and KIO7053 with 16 digital
Inputs) are available.
Both modules are configured via a Web browser and are queried by the AlarmManager over the network.
Commissioning and Configuration
Depending on the module type it can be powered via PoE or with an external power supply. Using a power
supply it is necessary to regard the information in the data sheet, or only to use a power supply delivered by
Kentix. Information for the wiring of the In- and Outputs can also be found in the data sheet.
Terminal assignment KIO7052
No
Connect the network port E1 to a network switch with PoE support. Connect
your PC to this switch respectively establish a network connection.
1
Open the Web-Interface of the module via the default IP 192.168.255.1 and
change the IP-settings in „Network Settings" to your required settings.
2
Default username and password: Admin/Admin
Start the Kentix ControlCenter and open the configuration of the I/O-module
3
via „Settings" -> „Advanced..." -> „External Alarms"
Proceed with the setup for the wired external Inputs:
Enter a name for the alarming and choose alarm assignment and the alarm
4
logic. Eventually enter another alarm delay (default 1 sec.). Also select an
alarm zone for every used input.
Save the configuration. After this the settings are directly active.
5
Page
64
Step
(06-2017, subject to change)
Terminal assignment KIO7053
Comment
If you use a switch without PoE establish power
supply via the connectors (R)+Vs and (B)-GND.
Use the supplied power adapter-cable.
In the section „Web HMI" the Inputs and
Outputs of the module can be monitored for
test purposes.
Select the module type and set the configured
IP-address.
In the module KIO7052 for each alarming state
one of the 8 Outputs is switched. Find the
assignment of the Outputs in the data sheet of
the module.
For testing purposes the state of the alarm
inputs can be monitored in the table
„MultiSensor Monitoring".