Expansion module for connection to the AlarmManager-PRO.
This module extends the external inputs of the AlarmManager on
additional 16 digital alarm inputs. Communication is via Ethernet, so
the module can be mounted anywhere. The configuration is done in
the software interface of the AlarmManager-PRO. The module
provides a build in web-server with for simple IP configuration and
testing of the inputs and outputs without any additional software.
Connection to Kentix AlarmManager-PRO
External Alarms of existing system equipment
(HVAC, UPS systems, generators, alarm systems, etc.)
Build in Web-Server (HTTP), Default IP: 192.168.255.1 (Admin/Admin)
KAM-IO communication via IP-PORT: 502 (Default)
ID, Password and IP-Filter
Plug-able screw-terminal for cables up to 1mm²
Digital dry contacts for potential-free wiring
ON:
Open

OFF:
Close to GND
Ethernet 1,5kVDC, I/O 3,7kVrms
Operation temperature -25°C to +75°C, Rel. humidity 10–90%
LAN 10/100 Base-TX
PoE (Class 1) or externes power supply 12–30VDC, 4.3Watt
72 x 123 x 35 mm (DIN-rail mounting)
KIO7053, Power supply 24VDC, manual
CE
Power-supply or PoE injector if no PoE supply is available
(06-2017, subject to change)
Pin assignment KIO7053
INPUT dry contact (High=1)
INPUT dry contact (Low=0)
kentix.com