4.10. SMS commands for remote control of AlarmManager

The AlarmManager reports not only all the alarms via SMS, it can be also remotely controlled via simple SMS
commands from a mobile phone. This brings the big advantage of having the central alarm system in your
pocket and remotely setting the system to the desired states.
The AlarmManager can be armed or disarmed and alarms can be acknowledged remotely. So you can decide if
it is necessary to intervene on the ground at any time by using the SMS information and status inquiry.
Important notes for remote control of the AlarmManagers via SMS
• Upper- and lower-case can be used.
• Between „Operator-PIN" and „COMMAND" is always a space.
• The „Operator-PIN" can have 4-8 alphanumerical characters. Setup the PIN with the ControlCenter.
• The AlarmManager is confirming each command SMS with an SMS back to the sender.
• Command SMS with the wrong phone number or password will not be confirmed for security reasons.
SMS control commands
SMS command
{PIN} ON
{PIN} ON{ZONE}
{PIN} OFF
{PIN} QUIT
{PIN} STATE
{PIN} MSTATE1-n
NOTE!
When a sensor sends an alarm, the SMS contains the number of the sensor to send a mstate request.
Example: Arm-disarming of the AlarmManager via SMS command

Page
18
Description
Arming of the AlarmManagers. All zones will be
armed.
Arming of the selected zone.
Disarming of all zones.
Acknowledge of all pending alarms. The alarm
repetition is terminated.
The AlarmManager can be set to arm state again.
The AlarmManager sends the actual system state.
The AlarmManager sends the actual system state
and values of a MultiSensor.
Enter the number of the MultiSensor (1-100)
directly after the command „MSTATE".

The response contains the name of the
MultiSensor.
1234 on
SMS command
OK! ARM ZONE 123
SMS answer
(06-2017, subject to change)
Example
Confirmation
1234 on
OK! ARM All Zones
1234 on1
OK! ARM ZONE 1
1234 off
OK! DISARM All Zones
1234 quit
OK! ALARM QUIT
OK! ARMED/DISARMED/
1234 state
ALARM
OK! SENSORNAME:
TEMP=20C
REL-HUM=25%
DEW-POINT=3C
1234 mstate1
MOTION=15%
EXT-IN=0
SABOTAGE=0
POWER=OK