Configuration In 8 Steps - Kentix AlarmManager-BASIC User Manual

Hide thumbs Also See for AlarmManager-BASIC:
Table of Contents

Advertisement

4.5. Configuration in 8 steps

No
Connect the AlarmManager via LAN cable to the PC. The yellow LED on the
1
LAN connector indicates a connection. Start the Kentix ControlCenter and
connect with the default IP-address 192.168.100.222 to the AlarmManager.
2
To change the network configuration open the menu item „Network".
To configure the different notification ways, use the menu item „E-Mail, SNMP &
GSM".
3
Enter the mobile data according to the used SIM card. When a PIN is used for
the SIM card, first „Save" your configuration with the correct PIN before inserting
the SIM card into the AlarmManager to avoid a lock of the card.
In the first user account enter your name, e-mail-address and mobile number in
international notation (+49 ...).
Assign an user password and a 4-digit Operator-PIN. The first user account is
4
always the "Administrator Account" and can not be deleted.

Using a KeyPad the PIN also applies to the operation via a KeyPad. Note that
the KeyPad allows only 4-digit passwords. To use the internal RFID card inside a
5
KeyPad also enter the RFID card number.
Press the "+" key to teach-in new devices such as MultiSensor or KeyPad.
BASIC: A new window opens and all accessible devices appear as soon as you
press the „learn button" at the device. After all devices are available in the list
press the "Save" button.

6
PRO: A windows opens where you can select RF- or LAN-components.
Selecting RF starts the scanning process as described in the BASIC-Version.
LAN-components have to be configured by entering the correct IP-address in
the „device address"-field.
In the list of devices you can already test functionality of the device. With a "right
7
click" you get a choice of test functions. Let the selected MultiSensor LED flash
and give the device a name.
Finally change the alarm settings and alarm assignments (Armed-Active /
Always-Active) according to your needs.
8
Changes made in the ControlCenter only become active when being saved into the AlarmManager.
Page
14
Step
Startup
Menu item „System - Settings"
Register tab „User accounts"
Register tab „Sensor-Devices"
Saving the configuration
IMPORTANT!
(06-2017, subject to change)
Comment
With 1:1 LAN connection via network cable
use crossover-adapter. Make sure that
your PC is in the same network.
You can disable the PIN of your SIM card
with a mobile phone. The entries in the
software will then be ignored.
You can test the e-mail and mobile settings
by pressing one of the test-buttons.
When controlling the AlarmManager via
your mobile phone the transmitted phone
number will be checked in addition to the
password.
When you run the teach-in process for RF-
devices a closed wireless network is
created, similar to an encrypted wireless
PC network. Make sure that the devices
are located in radio range close to the
AlarmManager / MultiSensor-LAN-RF.
Via the test functions you can switch also
the external outputs on or off.
Armed-Active: Alarms are only triggered,
when the system is in armed state.
Always-Active: Alarms are always
triggered, independent of the armed/
disarmed state of the system
kentix.com

Advertisement

Table of Contents
loading

Related Products for Kentix AlarmManager-BASIC

This manual is also suitable for:

Alarmmanager-pro

Table of Contents