E-Mail, SNMP & GSM
E-Mail
NOTE!
When the AlarmManager is registered for the Kentix360 cloud, all e-mails will be sent by the cloud-service. In
this case no e-mail-server is required, but recommended as a fallback option for additional redundancy.

When the AlarmManager is not able to sent messages via the cloud-service it will automatically send e-mails
via the configured SMTP server.
For e-mail notifications an account can be configured with optional user credentials. Depending on the e-mail
server, setting an encryption method might be necessary. When choosing the encryption mode (STARTTLS /
SSL) the required port will be set to the according default port. The port can be changed if required.
The e-mail notification can be testet directly in the settings using the orange checkbox.

NOTE!
The test e-mail is sent to the e-mail-address of the first user. In case of an error please check, whether an e-
mail-address has already been configured for this user. Also take care of possible restrictions (routing/firewalls)
in your network and synchronize data like encryption and communication port with the responsible persons.
SNMP - Monitoring
The AlarmManager supports full SNMP-functionality, therefore alarms can be sent as traps. Additionally the
AlarmManager can be configured for requests via network monitoring systems. For this purpose you can
download a MIB (Management Information Base) for the SNMP host.
GSM settings
Enter the mobile number and PIN of the SIM card.
Network monitoring
Configure up to 50 network devices (BASIC: 3 devices). For each device network services can be defined to be
monitored (ICMP Ping or TCP portcheck).
The AlarmManager periodically checks, if the specified services on the servers are available or if there is an
answer on a sent PING. The request interval can be set between 60 and 999 seconds. Note that the alarm will
be triggered after 3 failed attempts.
By pressing the Kentix-Check-Button the connection to the selected service can be tested.
In addition to the server monitoring function, the AlarmManager (PRO only) can receive incoming SNMP-Traps
as alarms. These will be sent to the users which are configured to be notified of always-active alarms. The
retrigger time of this service specifies the period of time after which the alarm can be sent again.
Page
20
(06-2017, subject to change)
kentix.com