When discharging condensate to an outside
drain caution must be taken to ensure
blockage cannot occur during freezing
conditions. If this is likely to occur, the use
of a condensate trap is recommended.
1
Ø21.5 mm min.
1000 mm min.
2
Ø100 mm min.
3
4
Fig. 22
External termination of condensate drain pipe to
absorption point
1
External length of pipe 3m max.
2
Plastic tube
3
Bottom of tube sealed
4
Limestone chippings
5
Two rows of three 12 mm holes at 25 mm centres, 50 mm
from bottom of tube and facing away from house
6
Hole depth
7
Ground (either/or)
8.2.11 CONNECTING THE CONDENSATE DRAIN PIPE
B Connect the condensate drain pipe to the condensate
trap (
fig. 23, [1] and fig. 24, [1]).
1
Fig. 23
Connecting the condensate trap
1
Condensate trap
6 720 648 726 (2011/07)
7
6
400 mm min.
5
6 720 648 726-022.1TD
6 720 648 726-023.1TD
1
Fig. 24
Condensate drainage pipe
1
Minimum distance > 2 cm
Observe the following regulations:
• The (local) waste water disposal regulations.
• The condensate trap in the connection kit must not be
permanently connected to the condensate drain pipe.
The minimum distance between the condensate trap
and the condensate drain pipe is 2 cm.
An air gap should be maintained between the boiler
condensate trap and the condensate pipework.
8.2.12 CONNECTING THE EXPANSION VESSEL IN A
SINGLE-BOILER SYSTEM
CAUTION: Damage to the installation due to
faulty pressure relief valve.
B The expansion vessel must be of
sufficient capacity.
B Connect the expansion tank to the boiler return
(CHR). If a non-return valve is available: connect the
expansion vessel to the CH-side of the non return
valve in the return circuit (
Fig. 25
Connecting the expansion vessel in a single-boiler
system
1
Expansion vessel
INSTALLATION
6 720 648 726-024.1TD
fig. 25, [1]).
1
6 720 648 726-025.1TD
25