Maintenance; Removing The Boiler Door; Cleaning The Heat Exchanger, Burner And Condensate Trap; Removing The Gas Valve - Worcester GB162-65 Installation And Servicing Instruction

Wall hung gas fired condensing boiler
Table of Contents

Advertisement

MAINTENANCE

13
MAINTENANCE
B Prepare the system for maintenance as described in
the chapter on Inspection (

13.1 REMOVING THE BOILER DOOR

If the boiler door cannot be fully opened, it may be
necessary to remove the door for inspection and
maintenance activities.
Proceed as follows:
B Unscrew the control panel from the boiler door and
hang it on the boiler frame (
screws", page 70).
B Unscrew the bolt from the left-hand top hinge of the
boiler door and remove it together with the washer.
B Slightly lift the door and pull it from the hinge. Put the
door upright in a safe position and make sure that it
cannot fall over.
The cover over the electrical connections
does not have to be removed from the
boiler.
Fig. 104 Removing the boiler door
64
section 12.1, page 61).
fig. 120 "Undoing the
6 720 648 726-104.1TD
13.2 CLEANING THE HEAT EXCHANGER,
BURNER AND CONDENSATE TRAP
The boiler has a self-cleaning coating.
WARNING: Damage to the installation due
to short circuits.
B Do not spray the detergent onto the
burner, the glow ignitor, the ionisation
electrode or other electrical components.

13.2.1 REMOVING THE GAS VALVE

B Undo the gas fitting screw connection [1] and pull the
4 connectors [2] from the gas valve.
GB162-65
GB162-80/100
Fig. 105 Undoing the connections to the gas fitting