Removing The Condensate Collector - Worcester GB162-65 Installation And Servicing Instruction

Wall hung gas fired condensing boiler
Table of Contents

Advertisement

B Disconnect the condensate trap from the coupling
and remove it [1].
1
Fig. 114 Disconnecting the condensate trap in the pump
group
B Rinse the condensate trap to clean it.
B Fill the condensate trap with approx. 1.0 ltr. water
before refitting it.
The condensate trap has a bayonet
connector. After inserting it, the condensate
trap must be turned clockwise through
¼ rotation until it clicks into place
(
fig. 17, page 23).

13.2.6 REMOVING THE CONDENSATE COLLECTOR

B Disconnect the flexible condensate drain hose and
bend it backwards.
Fig. 115 Removing the condensate trap hose
B Open the 2 clamps on the right and left at the bottom
of the condensate collector [1].
6 720 648 726 (2011/07)
B Pull the condensate collector down (step 1) and
remove it by pulling it towards you (step 2).
1
6 720 648 726-114.1TD
Fig. 116 Removing the condensate collector
B Check the condensate collector for damage and
replace it if required.
B Clean the condensate collector mechanically (using
compressed air or a soft brush) and rinse it with clean
water.
Fig. 117 Cleaning the condensate collector
6 720 648 726-115.1TD
MAINTENANCE
1
1
2
6 720 648 726-116.1TD
6 720 648 726-117.1TD
67