DIMENSIONS OF BOILER

Fig. 6
Dimensions and connections WITHOUT pump group (dimensions in mm)
CDO
Condensate drain outlet; Ø 24 mm O/D
CFO
Distance from wall bracket to center of horizontal flue elbow; 337.5 mm for Ø 80/125 flue and 339.5 mm for Ø 100/150 flue
CHF
CH (boiler) flow; G1½'' union nut with female thread
CHR
CH (boiler) return; G1½'' union nut with female thread
CS
Cap (DO NOT remove)
FGC/AIC
Flue gas/air intake connection: Ø 80/125 for GB162-65 and Ø 100/150 for GB162-80/100
GAS
Gas connection to boiler; G1'' female thread
The servicing clearances required are:
• in front:
50 mm
• below:
0 mm (250 mm with pump group)
• right side:
0 mm
• left side:
0 mm
• above:
30 mm.
The position selected for installation MUST allow
adequate space for servicing in front of the boiler:
• in front:
550 mm
• below:
350 mm
• right side:
0 mm
• left side:
0 mm
• above:
40 mm.
6 720 648 726 (2011/07)
550
465
152
AIC
FGC
CHF/CHR
GAS
CDO
35
138
162
6
520
0
AIC
FGC
300
CHF
GAS
CHR
CDO
39
130
130
140
DIMENSIONS OF BOILER
0
CS
6 720 648 726-006.1TD
17