When discharging condensate to an outside drain
caution must be taken to ensure blockage cannot occur
during freezing conditions. If this is likely to occur, the
use of a condensate trap is recommended.
1
Ø21.5 mm min.
1000 mm min.
2
Ø100 mm min.
3
4
Fig. 22 External termination of condensate drain pipe to absorption
point
[1]
External length of pipe 3 m max.
[2]
Plastic tube
[3]
Bottom of tube sealed
[4]
Limestone chippings
[5]
Two rows of three 12 mm holes at 25 mm centres, 50 mm from
bottom of tube and facing away from house
[6]
Hole depth
[7]
Ground (either/or)
8.2.11 Connecting the condensate drain pipe
▶ Connect the condensate drain pipe to the condensate trap
( fig. 23, [1] and fig. 24, [1]).
1
Fig. 23 Connecting the condensate trap
[1]
Condensate trap
6720813171 (2015/04)
7
6
400 mm min.
5
6 720 648 726-022.1TD
6 720 648 726-023.1TD
1
Fig. 24 Condensate drainage pipe
[1]
Minimum distance > 2 cm
Observe the following regulations:
• The (local) waste water disposal regulations.
• The condensate trap in the connection kit must not be permanently
connected to the condensate drain pipe. The minimum distance
between the condensate trap and the condensate drain pipe is 2 cm.
An air gap should be maintained between the boiler condensate trap and
the condensate pipework.
8.2.12 Connecting the expansion vessel in a single-boiler system
CAUTION: Damage to the installation due to faulty
pressure relief valve.
▶ The expansion vessel must be of sufficient capacity.
▶ Connect the expansion tank to the boiler return (CHR). If a non-return
valve is available: connect the expansion vessel to the CH-side of the
non-return valve in the return circuit ( fig. 25, [1]).
Fig. 25 Connecting the expansion vessel in a single-boiler system
[1]
Expansion vessel
Installation
6 720 648 726-024.1TD
1
6 720 648 726-025.1TD
19