4.4.1

Check Procedure

Landis+Gyr
48/88
1.
Check the
operating display is
shown. A flashing
'FF' shows fatal
errors.
2.
Check phases L1,
L2, and L3 are
present and in the
correct phase
sequence, i.e. L1-
L2-L3.
If one phase is not present or the voltage is < 45% Un, the relevant
symbol is absent. With the normal phase sequence the symbols are
displayed continuously.
If the meter is connected with reversed phase sequence (e.g. L2-L1-
L3) the symbols flash.
3.
The energy flow
arrows indicate
whether energy is
being imported (+)
or exported (-).
P = active energy,
Q = reactive
energy.
All segments of the
4.
display are
illuminated
Enter service menu
R
5.
Select menu item
6.
Enter installation
7.
diagnostic list
Check the phase
8.
voltages:
Voltage L1:
Voltage L2:
Voltage L3:
Check the phase
currents:
Current L1:
Current L2:
Current L3:
Code 32.7
Code 52.7
Code 72.7
Code 31.7
Code 51.7
Code 71.7
H 71 0200 0215 f en - ZMQ202 / ZFQ202 - User Manual
Operating display
Phase check
Energy flow
indicator
Display check
Set mode
Installation
diagnostic
Installation / De-installation