7
Maintenance
Note
7.1
Meter Tests
7.1.1
Measuring Times
7.1.2
Optical Test Outputs
7.1.3
Test Transmitting Contacts
H 71 0200 0215 f en - ZMQ202 / ZFQ202 - User Manual
Maintenance
Based on our experience as long-term meter manufacturers, electronic
meters require no maintenance.
Meter modifcation
No conversion, modification or retrofitting of the meter is allowed unless
stated in this chapter!
A meter accuracy check should be performed periodically according to
national regulations, usually every 8 years.
When testing the meter, the measuring conditions and the measuring
points must follow the IEC meter standards.
Use test equipment according to regulations for Cl.0.2S.
Metering Point
all-phase
1%In cos ϕ = 1
2%In cos ϕ = 0.5
100%In cos ϕ = 1
single phase
100%In cos ϕ = 0.5
The green optical test outputs supply pulses at a frequency dependent on
the load applied and the meter constant R. The pulse's rising edge is
always decisive for the test.
After switch on of voltage and current, wait 1 second for measurement to
be started.
The impulse frequency at nominal load Pn is between 4 and 6 Hz.
The test transmitting contacts are checked for accuracy with the same test
as for the optical test outputs.
Measuring Time
90 s
90 s
10 s
40 s
Landis+Gyr
75/88