Landis+Gyr ZMQ202 User Manual page 44

High precision metering
Table of Contents

Advertisement

Danger
Connect Current and Voltage Connectors
Connect Supply Inputs and Outputs and Transmitting Contacts
Landis+Gyr
44/88
Missing transformer earthing
Voltage transformers in medium and high voltage systems that are not
earthed on the secondary may reach dangerously high voltage values on
the secondary.
Voltage transformers are usually earthed on the secondary. If the voltage
transformer is not earthed, severe personal injury or death can result if
contact is made with the meter and the meter will be damaged beyond
repair.
If the voltage transformers are not earthed, special precautions must be
taken when working at the meter. Installation and de-installation of the
meter must only be performed by qualified meter installers, with strict
adherence to the utility's safety regulations.
1.
Shorten the current and voltage connecting wires to the required
length and then strip them to fit the connectors.
2.
Insert the current and voltage connecting wires to the terminal
numbers as shown in the connection diagram.
3.
Tighten (torque up to 1.7 Nm) the terminal screws using the torque
screwdriver size 2.
4.
Shorten the connecting wires of the supply inputs and outputs to the
required length and strip them for approx. 4 mm (wires and strands up
2
to 2.5 mm
can be connected).
5.
If stranded wire is used, it is recommended to fit it with ferrules for
connection.
6.
Connect the connecting wires of the supply inputs and outputs as
shown on the terminal connection diagram to the spring clamp
connectors as follows:
Insert a size 1 screwdriver, turning it slightly upwards, in
the upper opening.
Place the stripped connecting wire in the lower opening
and hold it there securely.
Withdraw the screwdriver. The connecting wire is now
firmly fixed.
H 71 0200 0215 f en - ZMQ202 / ZFQ202 - User Manual
Installation / De-installation

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Zfq202

Table of Contents