Table 50 - Non-Critical Status Diagnostic Message Table - Honeywell SmartLine Multivariable SMV800 Series User Manual

Hart/de option
Hide thumbs Also See for SmartLine Multivariable SMV800 Series:
Table of Contents

Advertisement

DE Diagnostic Messages,
Continued
SMV Status
SCT Status Message SFC Display Message TDC Status Message
9-3
Bad AP Compensation
PV4
9-4
Bad PT Compensation
PV4
2-6
Corrects Reset PV1
4-6
Corrects Reset PV2
Corrects Active on PV3 STATUS
8-6
Page 221
Table 49 - Non-Critical Status Diagnostic Message Table
BAD AP COMP PV4
STATUS
#
T A G I D .
BAD AP COMP PV4
BAD PT COMP PV4
STATUS
#
T A G I D .
BAD PT COMP PV4
CORRECTS RST PV1
STATUS
#
T A G I D .
CORRECTS RST PV1
CORRECTS RST PV2
STATUS
#
T A G I D .
CORRECTS RST PV2
CORR. ACTIVE PV3
#
T A G I D .
CORR. ACTIVE PV3
SMV800 Series HART/DE Option User's Manual
Possible Cause
Problem with absolute/gauge
pressure input PV2 or input
processing circuitry for PV2.
Problem with process temperature
input PV3, input processing
circuitry for PV3, or PV4 algorithm
parameter data.
All calibration "CORRECTS" were
deleted and data was reset for PV1
range.
All calibration "CORRECTS" were
deleted and data was reset.
Process temperature PV3 has
been calibrated and is now different
than
factory default (uncalibrated).
What to Do
• Verify that absolute/gauge
pressure input is correct for
selected flow equation.
• If error persists, replace
transmitter.
• Verify that process temperature
input is correct.
• Verify open/defective
temperature sensor.
• Correct process temperature
measurement.
• Check for temperature limits
exceeded in viscosity or density
configuration.
• Check design temperature value
for PV4 standard gas algorithm.
Recalibrate PV1 (DP) range.
Recalibrate PV2 (SP) range.
Nothing – or do a reset corrects
Revision 6.0