Diagnostics

7.2 Error Messages

The LCP shows all error messages on the status screen (below the index number). They are also shown in parameter 19-93
Error Status. Detailed information, additional notes on possible causes of errors, and tips for clearing errors can be found in
Table 7.2.
Parameter
Status/error message
19-93,
value
0
Status OK. No errors detected
1
Homing needed
2
Positive hardware limit exceeded
7
7
3
Negative hardware limit exceeded
4
Positive software limit exceeded
5
Negative software limit exceeded
6
VLT not running
7
Brake wear limit exceeded
8
Quick stop input activated
46
Operating Instructions
Meaning/cause
No errors detected.
A positioning command to a certain position has been issued while the home
position is not defined.
Clear the error and complete a homing sequence successfully before issuing
the next position command to the application.
The positive hardware switch input has been activated.
The application has hit the positive limit marker switch. Alternatively, the
connection to the limit switch has been lost or the limit switch is defective.
The negative hardware switch input has been activated.
The application has hit the negative limit marker switch. Alternatively, the
connection to the limit switch has been lost or the limit switch is defective.
A motor command has caused the software limit switch to be activated. The
maximum limit is specified in parameter 33-42 Positive Software End Limit.
Move the application back from the limit before clearing the error. If power
recovery is enabled in parameter 19-08 Power-Recovery, this can be done
through an error reset and a negative jog (input 54).
A motor command has caused the software limit switch to be activated. The
maximum limit is specified in parameter 33-41 Negative Software End Limit.
Move the application back from the limit before clearing the error. If power
recovery is enabled in parameter 19-08 Power-Recovery, this can be done
through an error reset and a positive jog (input 53).
The motor was not magnetised in a situation where it should have been. The
electromechanical brake is immediately activated in this case regardless of the
settings in parameters 19-12 Hold Delay and 19-06 Error Behaviour.
While the motor was holding/driving the load, the frequency converter either
tripped, connection to terminal X57/8 was lost, or the Hand On or Off key on
the LCP was pressed.
This error message is given if the motor has moved more than the allowed
number of user units specified in parameter 19-13 Brake Wear Limit while the
electronic brake was activated.
The mechanical brake is worn and must be replaced in the near future or the
limit specified in parameter 19-13 Brake Wear Limit is too low.
The quick stop input has been activated. As a safety precaution, the electro-
mechanical brake is activated according to the setting in parameter 19-06 Error
Behaviour and the motor is coasted regardless of the setting in parameter
19-09 Automatic Brake Control.
Clear the error to resume normal operation.