Danfoss MCO 351 Operating Instructions Manual page 37

Positioning controller vlt automationdrive fc 301/302
Hide thumbs Also See for MCO 351:
Table of Contents

Advertisement

Commissioning
32-67 Maximum Tolerated Position Error
Range:
Function:
revolution. This corresponds to 1 encoder
rotation.
WARNING
UNINTENDED START
The motor can restart unintentionally if the value of this
parameter is higher than the acceptable position
deviation.
Ensure that the value of this parameter is lower
than the acceptable position deviation.
32-68 Reverse Behaviour for Slave
This parameter determines the behaviour while moving in
reverse (moving in a negative direction).
Option:
[0]
Reversing allowed.
*
[1]
Reversing only allowed
when the master is reversed.
[2]
Reversing blocked.
32-69 Sampling Time for PID Control
Range:
Function:
2
[1–
Determines the sampling time of the position
*
1000
control algorithm. For example, increase the value
ms]
of the factory settings as follows:
For very low pulse frequencies, such as 1–
2 qc per sampling time: At least 10–20 qc
per sampling time are required.
For very slow systems with a long dead
time: If 1 ms is used here for control, large
motors will vibrate.
NOTICE
This value has a direct effect on the feed-
forward calculation. For example, if the
value in this parameter is doubled, then the
effectiveness of parameter 32-65 Velocity
Feed-Forward is halved.
32-70 Scan Time for Profile Generator
This parameter sets the sample time for the profile generator,
which is independent of the sample time for the PID controller.
For demanding background control tasks, the execution time of
the application programme may rise drastically. In such cases, the
profile generator scan time can be increased to 2. Values higher
than 2 ms provide hardly any benefits.
Option:
[1]
1 ms
[2]
2 ms
*
[3]
3 ms
[4]
4 ms
[5]
5 ms
MG33R302
Operating Instructions
0
Activation
Function:
0
0
Function:
Danfoss A/S © 04/2014 All rights reserved.
32-71 Size of the Control Window (Activation)
Range:
Function:
[0 to
The parameters 32-71 Size of the Control
*
1073741823 qc]
Window (Activation) and 32-72 Size of the
Control Window (Deactivation) are used to
turn the position control within defined
areas (control windows) on and off.
Parameter 32-71 Size of the Control Window
(Activation) indicates the size of the
window outside of which the control
should restart.
Control ON
Deactivation
Target
Deactivation
Size
Size
Control OFF
Illustration 5.3 Size of the Control Window
32-72 Size of the Control Window (Deactivation)
Range:
Function:
[0 to 1073741823
Indicates the size of the window inside
*
qc]
of which the control is to be
deactivated until parameter 32-71 Size
of the Control Window (Activation) is
reached again.
32-73 Integral Limit Filter Time
Range:
Function:
[–10000
Time in ms, which is used to increase or decrease
*
to 10000]
the integral limit of the position control loop up
to parameter 32-63 Limit Value for Integral Sum.
The integral part of the PID position control loop
can be active all the time, just during a
movement, or just at standstill. The value of this
parameter determines this behaviour.
Using value 0 activates the integral part of the
PID position control loop all the time according
to parameter 32-62 Integral Factor and the
limitation parameter 32-63 Limit Value for Integral
Sum.
Using a value >0 activates the integral part of the
PID position control loop just during a motor
movement. If the motor is at standstill, the
integral part is reduced to 0. If the motor starts
to move, the integration limit is increased from 0
to the defined value in 32-63 Limit Value for
Integral Sum within the period of time set in
parameter 32-73 Integral Limit Filter Time. If the
motor stops again, the integral part is reduced
again by decreasing the limit to 0 within the
defined period.
This handling of the integral part can be an
advantage for synchronisation applications, where
Control ON
Position
Activation
Size
Size
35
5
5

Advertisement

Table of Contents
loading

Table of Contents