Diagnostics; Troubleshooting - Danfoss MCO 351 Operating Instructions Manual

Positioning controller vlt automationdrive fc 301/302
Hide thumbs Also See for MCO 351:
Table of Contents

Advertisement

Diagnostics

7 Diagnostics

7.1 Troubleshooting

Problem
When a PID tracking error too big error (19-93 Error Status) occurs,
the inverter also trips on ALARM 13 (overcurrent)
Parameter 32-80 Maximum Velocity (Encoder) needs adjusting.
The frequency converter frequently trips on ALARM 7 (DC
Overvoltage) while ramping down.
The frequency converter frequently trips on ALARM 13 (overcurrent)
while ramping up.
The correct target position is reached, but the PID tracking error
(parameter 34-56 Track Error) is too big while the motor is turning.
The option sometimes forgets changes to trajectory data after a
power cycle.
Table 7.1 Troubleshooting
MG33R302
Operating Instructions
Solution
Check the velocity setting.
Check encoder for correct rotation direction.
Check encoder wiring and parameter configuration.
Check for correct brake handling.
Check velocity limits.
The time set in parameter 3-81 Quick Stop Ramp Time is too
short. Increase the setting.
Increase the setting in parameter 3-03 Maximum Reference. Doing
this also affects the performance of the parameters 32-60 Propor-
tional Factor to 32-66 Acceleration Feed-Forward.
Smaller changes to parameter 3-03 Maximum Reference may not
have any noticeable effect on most of these parameters but 32-65
Velocity Feed-Forward should always be recalculated using the auto-
calculation function 19-19 FFVEL Auto-calculation.
Use a higher ramp time setting in parameter 19-17 Jog Ramp
Time for jogging and parameter 19-26 Index Ramp Down Time for
positioning.
Check PCD [6] Quickbus Target Deceleration.
If a lower ramp time is required, install a brake resistor.
The ramp settings require too much torque. Determine which
operation (manual move or positioning) caused the trip, and
then set the corresponding ramp time (parameter 19-17 Jog
Ramp Time for jogging and parameter 19-25 Index Ramp Up Time
for positioning) with a higher ramp time setting.
Check PCD [5] Quickbus Target Acceleration.
The PID controller may be unstable – optimise the PID controller
parameters.
Harder settings of the PID controller may be required – optimise
the PID controller parameters.
Changes to trajectory data values are not saved after power-down
unless parameter 19-29 Parameter Save is activated before power-
down.
Danfoss A/S © 04/2014 All rights reserved.
7
7
45

Advertisement

Table of Contents
loading

Table of Contents