CAN Communication Mode between MBMS and BMS Cable Diagram:
Note: The 1
PowerCube-X1 should be installed in the same rack with MBMS.
st
3.6.3 ADD Switch Setting (Address Assignment)
ADD Switch is a 6 bit dial switches to manually distribute the
communication address of the battery system. Nether position is OFF,
means "0". Upper position is ON, means "1". 1
bit to 5
bit is for
st
th
address, and the 6
bit dial switch support a 120 Ω resistance
th
(Terminal Resistance).
Under CAN Communication Mode between MBMS and BMS (battery string qty. ≤6 set)
The MBMS's ADD Switch set with "1000X
X
". The last 2 bits are terminal resistances. X
=1; When the
1
0
0
CAN port communicate with only one another equipment, if this equipment uses terminal
resistance then X
should be "1", if this equipment uses without terminal resistance X
should be
1
1
"0"; If When the CAN port communicate with multi equipments, if this equipments uses terminal
resistance then X
should be set follow the CAN bus condition.
1
Note: X
address should correspond with CAN1 port, X
address should correspond with CAN0 port.
1
0