Rd Level Control Module (Mbms); Battery Maintenance - Pylontech PowerCube-X1 Operation Manual

Lithium-ion phosphate energy storage system
Hide thumbs Also See for PowerCube-X1:
Table of Contents

Advertisement

5.2.2.4 Install the new control module (BMS). And reconnect all the cables. Refer to chapter 3.5.
5.2.2.5 Turn on this battery string. Refer to chapter 3.6.
Caution: Before pull out the communication cables must mark the cable number, to avoid
cable wrong sequence.
5.2.3 Replacement of 3
5.2.3.1 Turn off the Power Switch. Refer to chapter 3.6.5.
Caution: Turn off this MBMS will stop the power output of belonging whole Battery Energy
Storage System.
5.2.3.2 Dismantle the 4 screws.
5.2.3.3 Install the new MBMS inside. And reconnect the cables. Refer to chapter 3.5.
5.2.3.4 Turn on this MBMS. Refer to chapter 3.6.
Caution: Before pull out the communication cables must mark the cable number, to avoid
cable wrong sequence.

5.3 Battery Maintenance

Danger: The maintenance of battery must done by qualified and authorized person only.
Danger: Some maintenance items must shut off at first.
5.3.1 Voltage Inspection:
[Periodical Maintenance] Check the voltage of battery system through the monitor system. Check
level Control Module (MBMS)
rd
24 / 31
18BISV0101