Cannot close the power
Switch.
5
Open the Power Relay
Switch, but the relay can't
be open.
5
Turn on the BMS. The Status
LED is flashing red.
6
Turn on the BMS. The Status
LED is lighting red. And the
buzzer is noising.
7
Turn on the BMS. The Status
LED shows normal. But the
output relay can't be
actuation.
8
Turn on the BMS. The one
and the following of the
battery module's Status
LED lighting red or not
lighting.
9
Single Cell is over voltage/
low voltage.
(Check through the
monitor or maintenance
software.)
10
Battery module shows the
temperature is -40℃.
Temperature, Low
Temperature or Failure
Protection.
DC Output breaker is
fault.
The main control board
is failure.
The wire of the output
relay, or the wire of the
power relay switch in
the BMS is broken
Self-check can't pass.
 Output relay is non-
separable switching,.
 The buzzer is failure;
 Output relay False
alarm;
The wire of the output
relay or the wire of the
power relay switch in
the BMS is broken.
 Power Relay Switch is
open;
 This battery module has
failure;
 Its communication cable
failure;
 Its Address Distribution
failure.
 Cell voltage sampling
failure.
 Cell failure;
The wires of temperature
sampling failure.
21 / 31
failure or not.
Check the DC output
breaker is fault or not. If it is
fault, change the control
module (BMS module).
Change the control
module (BMS module).
Check the wire got
loose or broken? Fix it.
Or the control module
(BMS module).
If something is wrong,
please contact with seller
or sells agent.
 Check the output relay.
If fault find out the short
circuit reason. Change
the relay or the control
module (BMS module).
 Change the control
module (BMS module).
Check the wire got
loose or broken? Fix it.
Or change the control
module (BMS module).
Close the Power Relay
Switch.
 Change this battery
module;
 Check the
communication cable;
 Check by professional
stuff.
 Check the wires of cell
sampling module;
 Change this battery
module.
Check the wires of
temperature sampling
18BISV0101