Set); System Turns On - Pylontech PowerCube-X1 Operation Manual

Lithium-ion phosphate energy storage system
Hide thumbs Also See for PowerCube-X1:
Table of Contents

Advertisement

The BMS's first five bits must set in below <BMS's Address Configure
Table>. The last BMS's terminal resistance must set in "1" (X=1), and other
BMS's terminal resistance must set in "0".
The address is configured follow ASCII code: ("X" is terminal resistance).
BMS's Address Configure Table:
Battery
Address Bit
String
1
10000X
2
01000X
3
11000X
4
00100X
5
10100X
6
01100X
7
11100X
8
00010X
Note: The above setting is following standard. But some PCS or Inverter's address is changeless,
can't be set. In this case the address setting must follow such equipment's address. If the address
setting is failed, please contact the distributor or Pylontech.

3.6.4 System turns on

Double check all the power cables and communication cables. Make sure the voltage of the
PCS is same level with the battery system. Check all the power switch of every battery system is
OFF.
Warning: MBMS must be turned on after all battery strings self-check finish.
(1) Check the UPS is turned on if configured. And the UPS is power supplying.
(2) Switch the external power or PCS on, make sure all the power equipments can work normally.
(3) Turn on the 1
BMS (Battery Control Modules) of battery string:
st
The second BMS must be operated after the first battery string's self-check is successful.
From 1st BMS to the last BMS Then turn on the battery strings on one by one from 1st BMS to the
last BMS.
Turn on the "POWER RELAY SWITCH":
Battery
Address Bit
String
9
10010X
10
01010X
11
11010X
12
00110X
13
10110X
14
01110X
15
11110X
16
00001X
15 / 31
Battery
Address Bit
String
17
10001X
18
01001X
19
11001X
20
00101X
21
10101X
22
01101X
23
11101X
24
00011X
Battery
Address Bit
String
25
10011X
26
01011X
27
11011X
28
00111X
29
10111X
30
01111X
31
11111X
32
00000X
18BISV0101