2.19 Monitoring Functions
Parameter 8415ΔI< BWD determines the pickup threshold for the differential current up to wire break leads
to differential protection blocking. If the differential current is greater than this threshold then a fault within
the protected object (e.g. transformer) is assumed and blocking of the differential protection is cancelled.
Asymmetrical measuring voltage failure "Fuse Failure Monitor"
The settings for the fuse failure monitor for single-phase measuring voltage failure (address 8426 FFM U<max
(3ph)), are to be selected such that reliable activation occurs if a phase voltage fails, but not such that false
activation occurs during earth faults Addresses 8422 FFM I< M1, 8423 FFM I< M2 and 8424 FFM I< M3
must be set as sensitive as required for the respective measuring location or side (with earth faults, below the
smallest fault current). This parameter can only be altered using DIGSI under Additional Settings.
In address 8403 FUSE FAIL MON. the fuse failure monitor can be switched off, e.g. during asymmetrical
testing.
Three-phase measuring voltage failure "Fuse Failure Monitor"
In address 8426 FFM U<max (3ph) the minimum voltage threshold is set. If the measured voltage drops
below this threshold and a simultaneous current jump is not detected while all three phase currents are
greater than the minimum current set for the respective side or measuring location (addresses 1111 to 1142).
This parameter can only be altered using DIGSI under Additional Settings.
2.19.3.3

Settings

Addresses which have an appended "A" can only be changed with DIGSI, under "Additional Settings".
The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secon-
dary nominal current of the current transformer.
Addr.
Parameter
2911A
FFM U>(min)
8401
BROKEN WIRE
8403
FUSE FAIL MON.
8414
T BWD delay
8415
ΔI< BWD
8422A
FFM I< M1
8423A
FFM I< M2
8424A
FFM I< M3
8426A
FFM U<max (3ph)
2.19.3.4

Information List

No.
Information
-
SysIntErr.
-
Error FMS1
266
C
Setting Options
10 .. 100 V
OFF
BWD Al and Blk
BWD Al and ABlk
BWD Al only
OFF
ON
0.0 .. 180.0 sec
0.05 .. 5.00 I/InO
1A
0.04 .. 2.00 A
5A
0.20 .. 10.00 A
1A
0.04 .. 2.00 A
5A
0.20 .. 10.00 A
1A
0.04 .. 2.00 A
5A
0.20 .. 10.00 A
2 .. 100 V
Type of
Comments
Informa-
tion
IntSP
Error Systeminterface
OUT
Error FMS FO 1
Default Setting
Comments
20 V
Minimum Voltage
Threshold U>
OFF
Fast broken current-wire
supervision
OFF
Fuse Failure Monitor
1.0 sec
Delay time for BWD super-
vision
1.00 I/InO
min differential current for
BWD
0.10 A
I< for FFM detection M1
0.50 A
0.10 A
I< for FFM detection M2
0.50 A
0.10 A
I< for FFM detection M3
0.50 A
5 V
Maximum Voltage
Threshold U< (3phase)
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016