Siemens SIPROTEC 4 7UT6 Series Manual page 360

Differential protection
Table of Contents

Advertisement

Mounting and Commissioning
3.3 Commissioning
The device also checks the matching factors between the rated currents of the CT's and the operational
currents of the protected object(s) as processed by the protection functions. If very high deviations combined
with sensitive protection settings are discovered an alarm is output which also indicates the suspicious setting
address(es).
In the operational or spontaneous annunciations also check if there are any fault annunciations from the
device.
Table 3-29
Message
No.
192
Error1A/
5Awrong
30097
Err. IN CT M1
to
to
30101
Err. IN CT M5
30102
Err.IN CT1..3
to
to
30105
Err.IN
CT10..12
30106
Err. IN CT IX1
to
to
30109
Err. IN CT IX4
311
FaultConfig/Se
t
312
GenErrGroup-
Conn
313
GenErrEarthCT
314
GenErrSides-
Meas
30067
par too low:
360
Indications on inconsistencies
Meaning
Setting of the rated secondary currents on input/output board incon-
sistent, general
Setting of the rated secondary currents inconsistent for the indicated
measured current input (3-phase inputs)
Setting of the rated secondary currents inconsistent for the indicated
measured current input (inputs for single-phase busbar protection)
Setting of the rated secondary currents inconsistent for the indicated
measured current input (single-phase inputs)
Group indication for configuration error
General: Error in transformer connection group
Error in single-phase inputs for earth fault differential protection
Error in assignment of sides and/or measuring locations
Parameter setting value too small for the indicated address number
Section
2.1.4 Power
System Data
1
3.1.2 Hard-
ware Modifi-
cations
("Switch
elements")
2.1.4 Power
System Data
1
3.1.2 Hard-
ware Modifi-
cations
("Switch
elements")
2.1.4 Power
System Data
1
3.1.2 Hard-
ware Modifi-
cations
("Switch
elements")
2.1.4 Power
System Data
1
3.1.2 Hard-
ware Modifi-
cations
("Switch
elements")
2.1.4 Power
System Data
1
2.1.4 Power
System Data
1
2.1.4 Power
System Data
1
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016
see