Siemens SIPROTEC 4 7UT6 Series Manual page 75

Differential protection
Table of Contents

Advertisement

Addr.
Parameter
256
AUX CT IX4 TYPE
261
VT SET
262
VT U4
263
VT U4 TYPE
270
Rated Frequency
271
PHASE SEQ.
276
TEMP. UNIT
311
UN-PRI SIDE 1
312
SN SIDE 1
313
STARPNT SIDE 1
314
CONNECTION S1
321
UN-PRI SIDE 2
322
SN SIDE 2
323
STARPNT SIDE 2
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016
Setting Options
1A/5A input
sensitiv input
Not connected
Side 1
Side 2
Side 3
Measuring loc.1
Measuring loc.2
Measuring loc.3
Busbar
Not connected
conn/not assig.
Side 1
Side 2
Side 3
Measuring loc.1
Measuring loc.2
Measuring loc.3
Busbar
Udelta transf.
UL1E transform.
UL2E transform.
UL3E transform.
UL12 transform.
UL23 transform.
UL31 transform.
Ux transformer
50 Hz
60 Hz
16,7 Hz
L1 L2 L3
L1 L3 L2
Celsius
Fahrenheit
0.4 .. 800.0 kV
0.20 .. 5000.00 MVA
Earthed
Isolated
Y
D
Z
0.4 .. 800.0 kV
0.20 .. 5000.00 MVA
Earthed
Isolated
Default Setting
Comments
1A/5A input
Type of auxiliary CT IX4
Measuring loc.1
VT set UL1, UL2, UL3 is assigned
Measuring loc.1
VT U4 is assigned
Udelta transf.
VT U4 is used as
50 Hz
Rated Frequency
L1 L2 L3
Phase Sequence
Celsius
Unit of temperature measurement
110.0 kV
Rated Primary Voltage Side 1
38.10 MVA
Rated Apparent Power of Transf.
Side 1
Earthed
Starpoint of Side 1 is
Y
Transf. Winding Connection Side 1
11.0 kV
Rated Primary Voltage Side 2
38.10 MVA
Rated Apparent Power of Transf.
Side 2
Earthed
Starpoint of Side 2 is
Functions
2.1 General
75