Frequency Protection - Siemens SIPROTEC 4 7UT6 Series Manual

Differential protection
Table of Contents

Advertisement

4.16

Frequency Protection

Measuring Range of the Frequency Functions
Lower frequency limit
Upper frequency limit
Minimum positive sequence
voltage for frequency measure-
ment (phase-phase voltage)
Minimum positive sequence
voltage for frequency measure-
ment (non-interlinked voltage)
Setting Ranges / Increments
Number of frequency elements
Pickup values f<, f<<, f<<<
Pickup value f>
Delay times T f<<
Delay times T f<, T f<<<,T f>
Undervoltage blocking
(positive sequence component U
The set times are pure delay times
1)
No pickup is effected below the minimum voltage for frequency measurement
Times
Pickup times f>, f<
Dropout times f>, f<
Dropout difference
Δf = | Pickup Value – Dropout Value |
Dropout ratio
Dropout ratio for Undervoltage Blocking
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016
Rated frequency 50/60/16.7 Hz
Rated frequency 50/60 Hz
Rated frequency 16.7 Hz
approx. 8.6 V
approx. 5 V
4; can be set to f<, f<<, f<<< or f>
Rated frequency 50 Hz
Rated frequency 60 Hz
Rated frequency 16.7 Hz
Rated frequency 50 Hz
Rated frequency 60 Hz
Rated frequency 16.7 Hz
0.00 s to 600.00 s
or ∞ (disabled)
0.00 s to 100.00 s
or ∞ (disabled)
10.0 V to 125.0 V and
)
0 V
(no blocking)
1)
1
50/60 Hz
16.7 Hz
50/60 Hz
16.7 Hz
approx. 20 mHz
approx. 1.10
Technical Data
4.16 Frequency Protection
approx. 9.25 Hz
approx. 70 Hz
approx. 23.33 Hz
40.00 to 49.99 Hz
or 0 (disabled)
50.00 to 59.99 Hz
or 0 (disabled)
10.00 to 16.69 Hz
or 0 (disabled)
50.01 to 66.00 Hz
or ∞ (disabled)
60.01 to 69.99 Hz
or ∞ (disabled)
60.01 to 69.99 Hz
or ∞ (disabled)
Increments 0.01 s
Increments 0.01 s
Increments 0.1 V
approx. 100 ms
approx. 300 ms
approx. 160 ms
approx. 480 ms
451