Time Overcurrent Protection for Earth Current

General

2.5.1
The time overcurrent protection for earth current is assigned to a 1-phase measured current input of the
device. It can be used for any desired single-phase application. Its preferred application is the detection of an
earth current between the starpoint of a protective object and its earth electrode (that's why the description).
The corresponding one-phase additional measuring input has to be correctly assigned to the one-phase
current transformer of the power plant.
This protection can be used in addition to the restricted earth fault protection (Section
Fault
Protection). Then it forms the backup protection for earth faults outside the protected zone which are
not cleared there.
The time overcurrent protection for earth current provides two definite time stages (O) and one inverse time
stage (C). The latter may operate according to an IEC or an ANSI, or a user defined characteristic.
[ueb-erd-reservesch-020926-st, 1, en_GB]
Figure 2-79
7UT612 is equipped with one, 7UT613/63x with two time overcurrent protection functions that can be used
independently of each other and for different locations. Allocation of the respective protection functions to
the single-phase measuring locations were done according to Section
tions to Measuring Locations /
2.5.2

Definite Time, Instantaneous Overcurrent Protection

The definite time stages (O) for earth current are always available even if an inverse time characteristic has
been configured in the scope of functions (see Section
Pickup, Trip
Two definite time stages are available for the earth current.
For the IE>> stage, the current measured at the assigned 1-phase current input is compared with the setting
value IE>>. Current above the pickup value is detected and annunciated. When the delay time T IE>> has
expired, tripping command is issued. The reset value is approximately 95 % below the pickup value for
currents above Ι
near the pickup value (e.g. 20 % at 0.1 · Ι
The following figure shows the logic diagram for the high-current stage IE>>.
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016
Time overcurrent protection as backup protection for restricted earth fault protection
Sides.
. Lower values require a higher hysteresis in order to avoid intermittent pickup on currents
N
).
N
2.5 Time Overcurrent Protection for Earth Current