Siemens SIPROTEC 4 7UT6 Series Manual page 213

Differential protection
Table of Contents

Advertisement

Addr.
Parameter
9041A
RTD 4 TYPE
9042A
RTD 4 LOCATION
9043
RTD 4 STAGE 1
9044
RTD 4 STAGE 1
9045
RTD 4 STAGE 2
9046
RTD 4 STAGE 2
9051A
RTD 5 TYPE
9052A
RTD 5 LOCATION
9053
RTD 5 STAGE 1
9054
RTD 5 STAGE 1
9055
RTD 5 STAGE 2
9056
RTD 5 STAGE 2
9061A
RTD 6 TYPE
9062A
RTD 6 LOCATION
9063
RTD 6 STAGE 1
9064
RTD 6 STAGE 1
9065
RTD 6 STAGE 2
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016
Setting Options
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
-50 .. 250 °C; ∞
2.10 RTD-Boxes for Overload Detection
Default Setting
Comments
Not connected
RTD 4: Type
Other
RTD 4: Location
100 °C
RTD 4: Temperature Stage 1
Pickup
212 °F
RTD 4: Temperature Stage 1
Pickup
120 °C
RTD 4: Temperature Stage 2
Pickup
248 °F
RTD 4: Temperature Stage 2
Pickup
Not connected
RTD 5: Type
Other
RTD 5: Location
100 °C
RTD 5: Temperature Stage 1
Pickup
212 °F
RTD 5: Temperature Stage 1
Pickup
120 °C
RTD 5: Temperature Stage 2
Pickup
248 °F
RTD 5: Temperature Stage 2
Pickup
Not connected
RTD 6: Type
Other
RTD 6: Location
100 °C
RTD 6: Temperature Stage 1
Pickup
212 °F
RTD 6: Temperature Stage 1
Pickup
120 °C
RTD 6: Temperature Stage 2
Pickup
Functions
213