Time Overcurrent Protection For Residual Current - Siemens SIPROTEC 4 7UT6 Series Manual

Differential protection
Table of Contents

Advertisement

Technical Data

4.4 Time Overcurrent Protection for Residual Current

4.4
Time Overcurrent Protection for Residual Current
Characteristics
Definite-time stages
Inverse time stages
(acc. to IEC or ANSI)
Reset characteristics
(with disk emulation)
Current Stages
High current stages
Definite time current elements
(50Ns-2, 50Ns-1)
Inverse current elements (51Ns-
IEC)
Inverse current elements (51Ns-
ANSI)
Tolerances with inverse time
Currents
Times
416
DT
>>, 3Ι
>>, Ι
Ι
Ph
0
IT
, 3Ι
Ι
P
0P
one of the tripping curves depicted in
Figure 4-7
side may be selected; alternatively user speci-
fied trip and reset characteristic
IT
For illustrations of possible reset time charac-
teristics see
left-hand side.
>>
Ι
0.10 A to 35.00 A
Ph
or ∞ (ineffective)
T
0.00 s to 60.00 s
ΙPh>>
or ∞ (no trip)
>>
0.10 A to 35.00 A
0
or ∞ (ineffective)
T
0.00 s to 60.00 s
3Ι0>>
or ∞ (no trip)
>
Ι
0.10 A to 35.00 A
Ph
or ∞ (ineffective)
T
0.00 s to 60.00 s
ΙPh>
or ∞ (no trip)
>
0.10 A to 35.00 A
0
or ∞ (ineffective)
T
0.00 s to 60.00 s
3Ι0>
or ∞ (no trip)
0.10 A to 4.00 A
Ι
P
T
0.05 s to 3.20 s
ΙP
or ∞ (no trip)
0.05 A to 4.00 A
0P
T
0.05 s to 3.20 s
3Ι0P
or ∞ (no trip)
0.10 A to 4.00 A
Ι
P
D
0.50 s to 15.00 s
ΙP
or ∞ (no trip)
0.05 A to 4.00 A
0P
D
0.50 s to 15.00 s
3Ι0P
or ∞ (no trip)
2)
3 % of set value or 1 % rated current
1 % of set value or 10 ms
>, 3Ι
>
Ph
0
to
Figure 4-12
on the right-hand
Figure 4-7
to
Figure 4-12
Increments 0.01 A
1)
Increments 0.01 s
Increments 0.01 A
1)
Increments 0.01 s
Increments 0.01 A
1)
Increments 0.01 s
Increments 0.01 A
1)
Increments 0.01 s
Increments 0.01 A
1)
Increments 0.01 s
Increments 0.01 A
1)
Increments 0.01 s
Increments 0.01 A
1)
Increments 0.01 s
Increments 0.01 A
1)
Increments 0.01 s
C53000-G1176-C230-5, Edition 09.2016
on the
SIPROTEC 4, 7UT6x, Manual

Hide quick links: