3.4

Final Preparation of the Device

The used terminal screws must be tightened, including those that are not used. All the plug connectors must
be correctly inserted.
!
CAUTION
Do not use force!
The permissible tightening torque must not be exceeded as the threads and terminal chambers may
otherwise be damaged!
²
The setting values should be checked again, if they were changed during the tests. Check in particular
whether all protection, control and auxiliary functions to be found with the configuration parameters are set
correctly ( see Section
Keep a copy of all of the in-service settings on a PC.
The user should check the device-internal clock and set/synchronize it if necessary, provided that it is not
synchronised automatically. For further information refer to
The indication buffers are deleted under Main Menu → Annunciation Set/Reset, so that in the future they
only contain information on actual events and states. The numbers in the switching statistics should be reset
to the values that were existing prior to the testing.
The counters of the operational measured values (e.g. operation counter, if available) are reset under Main
Menu → Measurement → Reset.
Press the ESC several times if necessary, to return to the default display. The basic window appears in the
display (e.g. display of operation measured values).
Clear the LEDs on the front panel by pressing the LED key, so that they only show real events and states. In so
doing, possibly stored output relays will also be reset. Pressing the LED key also serves as a test for the LEDs
on the front panel because they should all light up when the button is pressed. Any LEDs that are lit after the
clearing attempt are displaying actual conditions.
The green "RUN" LED must light up, whereas the red "ERROR" must not light up.
If a test switch is available, it must be in the operating position.
The device is now ready for operation.
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016
2.1.3 Functional
Scope) and that all desired elements and functions have been set ON.
Mounting and Commissioning
3.4 Final Preparation of the Device
/1/ SIPROTEC 4 System
Manual.