Siemens SIPROTEC 4 7UT6 Series Manual page 578

Differential protection
Table of Contents

Advertisement

Functions, Settings, Information
F.2 Settings
Addr. Parameter
4433
HOT-SPOT GR
5001
REVERSE POWER
5011
P> REVERSE
5012
Pr pick-up
5013
T-SV-OPEN
5014
T-SV-CLOSED
5015A T-HOLD
5016A Type of meas.
5101
FORWARD POWER
5111
Pf<
5112
P< fwd
5113
T-Pf<
5114
Pf>
5115
P> fwd
5116
T-Pf>
5117A MEAS. METHOD
5201
UNDERVOLTAGE
5211
U<
5212
U<
5213
T U<
5214
U<<
5215
U<<
5216
T U<<
5217A DOUT RATIO
5301
OVERVOLTAGE
5311
U>
5312
U>
5313
T U>
5314
U>>
5315
U>>
578
Function
C
Setting Options
Therm.Over-
22 .. 29
load2
Reverse Power
OFF
ON
Block relay
Reverse Power
1A
-3000.00 .. -0.85 W -8.70 W
5A
-15000.00 ..
-4.25 W
Reverse Power
-17.000 ..
-0.005 P/SnS
Reverse Power
0.00 .. 60.00 sec; ∞ 10.00 sec
Reverse Power
0.00 .. 60.00 sec; ∞ 1.00 sec
Reverse Power
0.00 .. 60.00 sec; ∞ 0.00 sec
Reverse Power
accurate
fast
Forward Power
OFF
ON
Block relay
Forward Power 1A
1.7 .. 3000.0 W
5A
8.5 .. 15000.0 W
Forward Power
0.01 .. 17.00 P/SnS
Forward Power
0.00 .. 60.00 sec; ∞ 10.00 sec
Forward Power 1A
1.7 .. 3000.0 W
5A
8.5 .. 15000.0 W
Forward Power
0.01 .. 17.00 P/SnS
Forward Power
0.00 .. 60.00 sec; ∞ 10.00 sec
Forward Power
accurate
fast
Undervoltage
OFF
ON
Block relay
Undervoltage
10.0 .. 125.0 V
Undervoltage
0.10 .. 1.25 U/UnS
Undervoltage
0.00 .. 60.00 sec; ∞ 3.00 sec
Undervoltage
10.0 .. 125.0 V
Undervoltage
0.10 .. 1.25 U/UnS
Undervoltage
0.00 .. 60.00 sec; ∞ 0.50 sec
Undervoltage
1.01 .. 1.20
Overvoltage
OFF
ON
Block relay
Overvoltage
30.0 .. 170.0 V
Overvoltage
0.30 .. 1.70 U/UnS
Overvoltage
0.00 .. 60.00 sec; ∞ 3.00 sec
Overvoltage
30.0 .. 170.0 V
Overvoltage
0.30 .. 1.70 U/UnS
Default Setting
Comments
22
Hot-spot to top-oil
gradient
OFF
Reverse Power Protection
P> Reverse Pickup
-43.50 W
-0.050 P/SnS
Pick-up threshold reverse
power
Time Delay Long (without
Stop Valve)
Time Delay Short (with
Stop Valve)
Pickup Holding Time
accurate
Type of measurement
OFF
Forward Power Supervi-
sion
17.3 W
P-forw.< Supervision
Pickup
86.5 W
0.10 P/SnS
Pick-up threshold P<
T-P-forw.< Time Delay
164.5 W
P-forw.> Supervision
Pickup
822.5 W
0.95 P/SnS
Pick-up threshold P>
T-P-forw.> Time Delay
accurate
Method of Operation
OFF
Undervoltage Protection
75.0 V
U< Pickup
0.75 U/UnS
Pick-up voltage U<
T U< Time Delay
65.0 V
U<< Pickup
0.65 U/UnS
Pick-up voltage U<<
T U<< Time Delay
1.05
U<, U<< Drop Out Ratio
OFF
Overvoltage Protection
115.0 V
U> Pickup
1.15 U/UnS
Pick-up voltage U>
T U> Time Delay
130.0 V
U>> Pickup
1.30 U/UnS
Pick-up voltage U>>
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016