Siemens SIPROTEC 4 7UT6 Series Manual page 401

Differential protection
Table of Contents

Advertisement

Maximum Distance of Transmission 3,280 ft or 1,000 m at ≤ 93.75 kBd
Profibus FO (FMS and DP)
FO connector type
Connection for flush-mounted
casing
Connection for surface-mounted
casing
Transmission Speed
recommended:
Optical Wavelength
Laser Class 1 according to EN
60825-1/-2
Permissible Optical Link Signal
Attenuation
Maximum Distance of Transmission max. 0.93 miles (1.5 km)
DNP3.0 / MODBUS RS485
Connection for flush-mounted
casing
Connection for surface-mounted
casing
Test Voltage
Transmission Speed
Maximum Distance of Transmission max. 0.62 miles (1 km)
DNP3.0 / MODBUS / FO
FO connector type
Connection for flush-mounted
casing
Connection for surface-mounted
casing
Transmission Speed
Optical Wavelength
Laser Class 1 according to EN
60825-1/-2
Permissible Optical Link Signal
Attenuation
Maximum Distance of Transmission max. 0.93 miles (1.5 km)
Ethernet electrical (EN100) for DIGSI, IEC61850
Connection for flush-mounted
casing
Connection for surface-mounted
casing
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016
500 m or 1,640 ft at ≤ 187.5 kBd
200 m or 330 ft at ≤ 1.5 MBd
ST connector
Single ring / double ring according to the order for FMS; for DP only
double ring available
Rear panel, mounting location "B"
in console housing on the case bottom via RS485 and external RS485/
optical converter
up to 1.5 MBd
1)
> 500 kBd with normal casing
≤ 57 600 Bd at detached operator panel
λ = 820 nm
using glass fiber 50/125 μm or using glass fiber 62.5/125 μm
max. 8 dB, with glass fiber 62.5/125 μm
Rear panel, mounting location "B", 9-pin DSUB miniature connector
at the housing mounted case on the case bottom
AC 500 V; 50 Hz
up to 19,200 Bd
1)
ST–Connector Receiver/Transmitter
Rear panel, mounting location "B"
not available
up to 19,200 Bd
1)
λ = 820 nm
using glass fiber 50/125 μm or using glass fiber 62.5/125 μm
max. 8 dB, with glass fiber 62.5/125 μm
rear panel, mounting location "B"; 2 x RJ45 socket contact 100BaseT acc.
to IEEE802.3
in console housing at case bottom
Technical Data
4.1 General
401

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents