Parameterisation Error - Siemens SIPROTEC 4 7UT6 Series Manual

Differential protection
Table of Contents

Advertisement

Functions
2.19 Monitoring Functions
Monitoring
Broken wire
Circuit Breaker
EN100 Module
CFC
Fuse-Failure-Monitor
(asymmetrical and
symmetrical)
Trip circuit supervision
1)
After three unsuccessful attempts, the device is put out of operation
2)
DOK = "Device Okay" = relay ("Life-contact")
2.19.5

Parameterisation Error

Changes made in settings during allocation of binary inputs and outputs or during assignment of measuring
inputs, may lead to inconsistencies endangering proper operation of protective and supplementary functions.
The device 7UT6x controls the settings for consistency and announces any inconsistent settings. For instance,
earth fault differential protection cannot be applied if there is no measuring input for the starpoint current
between starpoint of the protected object and the earthing electrode.
These inconsistencies are output with the operational and spontaneous annunciations.
270
Possible Causes
external (current trans-
former secondary circuit)
Circuit breaker tripping
external wiring/
EN100 Module
Internal
External (voltage trans-
former secondary circuit)
External (trip circuit or
control voltage)
Malfunction
Indication (No.)
Response
All respective protec-
brk. wire IL1M1
tion functions are
brk. wire IL2M1
blocked
brk. wire IL3M1
...
brk. wire IL1M5
brk. wire IL3M5
brk. wire IL3M5
Alarm with identifica-
Incons.CBaux M1
tion of the measuring
...
location/side
Incons.CBaux M5
or
Incons.CBaux S1
...
Incons.CBaux S5
Alarm
Fail Ch1
Fail Ch2
or
Failure Modul
Alarm
Distur.CFC
Blocked alarm of
„Fuse–Failure"
dependent under-
voltage function.
Alarm
FAIL: Trip cir.
C53000-G1176-C230-5, Edition 09.2016
Output
as allocated
as allocated
as allocated
as allocated
as allocated
as allocated
SIPROTEC 4, 7UT6x, Manual