Buffer Memory Address Comparison - Mitsubishi Electric MELSEC L Series Manual

Small type s intelligent function modules
Hide thumbs Also See for MELSEC L Series:
Table of Contents

Advertisement

2
ANALOG INPUT MODULE REPLACEMENT

2.4.4 Buffer memory address comparison

Sequence programs need to be changed because the buffer memory address assignment differs.
For details of the buffer memory areas and sequence programs, refer to the MELSEC-L Analog-Digital
Converter Module User's Manual.
A1S68AD
Address
Name
(decimal)
0
A-D conversion enable/disable
1
Write data error code
2
Average processing specification
3
4
5
6
System area (Use prohibited)
7
8
9
10
CH1 Average time, count
11
CH2 Average time, count
12
CH3 Average time, count
13
CH4 Average time, count
14
CH5 Average time, count
15
CH6 Average time, count
16
CH7 Average time, count
17
CH8 Average time, count
18
System area (Use prohibited)
19
20
CH1 Digital output value
21
CH2 Digital output value
22
CH3 Digital output value
23
CH4 Digital output value
24
CH5 Digital output value
25
CH6 Digital output value
26
CH7 Digital output value
27
CH8 Digital output value
28
A/D conversion completed flag
29
System area (Use prohibited)
2
- 32
Address
Read/write
(decimal)
R/W
0
A/D conversion enable/disable setting
R
1
CH1 Time Average/ Count Average/Moving Average
R/W
2
CH2 Time Average/ Count Average/Moving Average
3
CH3 Time Average/ Count Average/Moving Average
4
CH4 Time Average/ Count Average/Moving Average
5
CH5 Time Average/ Count Average/Moving Average
6
CH6 Time Average/ Count Average/Moving Average
7
CH7 Time Average/ Count Average/Moving Average
8
CH8 Time Average/ Count Average/Moving Average
Averaging process setting (The setting is not required
9
when the A1S68AD is replaced.)
10
A/D conversion completed flag
11
CH1 Digital output value
12
CH2 Digital output value
13
CH3 Digital output value
R/W
14
CH4 Digital output value
15
CH5 Digital output value
16
CH6 Digital output value
17
CH7 Digital output value
18
CH8 Digital output value
19
Latest error code
20
Setting range (CH1 to CH4)
21
Setting range (CH5 to CH8)
22
Offset/gain setting mode Offset specification
23
Offset/gain setting mode Gain specification
R
24
Averaging process setting (CH1 to CH4)
25
Averaging process setting (CH5 to CH8)
26
System area
Input signal error detection extension setting (CH1 to
27
CH4)
Input signal error detection extension setting (CH5 to
R/W
28
CH8)
29
System area
30
CH1 Maximum value
31
CH1 Minimum value
32
CH2 Maximum value
33
CH2 Minimum value
34
CH3 Maximum value
35
CH3 Minimum value
36
CH4 Maximum value
37
CH4 Minimum value
38
CH5 Maximum value
39
CH5 Minimum value
40
CH6 Maximum value
41
CH6 Minimum value
42
CH7 Maximum value
43
CH7 Minimum value
44
CH8 Maximum value
45
CH8 Minimum value
46
System area
47
Input signal error detection setting
48
Warning output setting
L60ADVL8/L60ADIL8
Name
Read/write
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R/W
R/W
R/W
R/W
R/W
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W
R/W