ANALOG INPUT MODULE REPLACEMENT
L60ADVL8
-10 to 10VDC
(Input resistance value: 1.8M)
16-bit signed binary
(-16384 to 16383, when the scaling function
is used: -32768 to 32767)
Analog input range
0 to 10V
0 to 5V
1 to 5V
Voltage
-10 to 10V
1 to 5V (Extended mode)
User range setting
0 to 20mA
4 to 20mA
Current
4 to 20mA
(Extended mode)
User range
Analog input range
0 to 10V
Within ±0.2% (±32 digit)
0 to 5V
Within ±0.2% (±16 digit)
1 to 5V
Voltage
-10 to 10V
Within ±0.2% (±32 digit)
1 to 5V
Within ±0.2% (±16 digit)
(Extended mode)
0 to 20mA
4 to 20mA
Current
Within ±0.2% (±16 digit)
4 to 20mA
(Extended mode)
Voltage: ±15V
8 channels/module
Between the I/O terminal and programmable controller power supply: Photocoupler
Between input channels: Not insulated
Between the I/O terminal and programmable controller power supply: 500VACrms, for 1
Between the I/O terminal and programmable controller power supply: 500VDC, 10M or
16 points (I/O assignment: intelligent 16 points)
18-point terminal block
R1.25-3 (Solderless terminals with an insulation sleeve cannot be used.)
0.20A
L60ADIL8
0 to 20mA
(Input resistance value: 250)
16-bit signed binary
(-8192 to 8192, when the scaling function is
used: -32768 to 32767)
Digital output value
0 to 16000
0 to 8000
-16000 to 16000
-2000 to 9000
-8000 to 8000
0 to 8000
-2000 to 9000
-8000 to 8000
Ambient temperature
25±5°C
0 to 55°C
Within ±1% (±160 digit)
Within ±1% (±80 digit)
Within ±1% (±160 digit)
Within ±1% (±80 digit)
Within ±1% (±80 digit)
1ms/channel
Current: ±30mA
Up to 10000 times
minute
higher
2
0.3 to 0.75mm
0.21A
0.19kg
: Compatible,
Compatibility
Resolution
625µV
500µV
625µV
500µV
414µV
2500nA
2000nA
2500nA
1660µA
×
×
×
: Partial change required, ×: Incompatible
Precautions for replacement
The voltage and current cannot be mixed in one
module.
Since the resolution differs between AnS series
and L series modules, it needs to be matched
using a sequence program, user range settings,
or the scaling function (refer to Appendix 3).
The number of occupied I/O points is changed to
16 points.
Wiring needs to be changed.