3
ANALOG OUTPUT MODULE REPLACEMENT

3.2 A1S62DA

3.2.1 Performance specifications comparison

Item
Digital input
Analog output
I/O characteristics
Maximum resolution
Overall accuracy
(Accuracy for the maximum analog
output value)
Maximum conversion speed
Absolute maximum output
Number of analog output channels
Number of offset/gain settings
Output short protection
3
- 3
voltage: -4000 to 4000, current: 0 to 4000
voltage: -8000 to 8000, current: 0 to 8000
voltage: -12000 to 12000, current: 0 to 12000
Voltage: -10 to 0 to +10VDC
(External load resistance value: 2K to 1M)
(External load resistance value: 0 to 600)
Resolution
1/4000
4000
2000
Digital input
0
value
-2000
-4000
*1 The offset value is set to 0V and the gain value is set to 10V (factory default setting).
*2 The offset value is set to 4mA and the gain value is set to 20mA.
1/4000
1/8000
1/12000
(voltage: ±100mV, current: ±200µA)
A1S62DA
1/4000 setting:
1/8000 setting:
1/12000 setting:
Current: 0 to 20mA
Voltage output
1/8000
1/12000
value
8000
12000
10V
4000
6000
5V
0
0
0
-4000
-6000
-5V
-8000
-12000
-10V
2.5mV (10V)
5µA (20mA)
1.25mV (10V)
2.5µA (20mA)
0.83mV (10V)
1.7µA (20mA)
±1%
Within 25ms/2 channels
(same for 1 channel)
Voltage: ±12V
Current: +28mA
2 channels/module
Available
Current output
*1
*2
value
20mA
12mA
4mA