Mitsubishi Electric MELSEC L Series Manual page 65

Small type s intelligent function modules
Hide thumbs Also See for MELSEC L Series:
Table of Contents

Advertisement

3
ANALOG OUTPUT MODULE REPLACEMENT
(-20480 to 20479, When the scaling function is used: -32768 to 32767)
Voltage: -10 to 10VDC (External load resistance value: 1K to 1M)
Current: 0 to 20mA (External load resistance value: 0 to 600)
Analog output range
0 to 5V
1 to 5V
Voltage
-10 to 10V
User range settings
0 to 20mA
Current
4 to 20mA
User range settings
Ambient temperature 25±5°C: within ±0.1%
(voltage: ±10mV, current: ±20µA)
Ambient temperature 0 to 55°C: within ±0.3%
(voltage: ±30mV, current: ±60µA)
L60DA4
16-bit signed binary
Digital value
Maximum resolution
0 to 20000
-20000 to 20000
0 to 20000
-20000 to 20000
20µs/channel
4 channels/module
Up to 50000 times
Available
: Compatible,
Compatibility
250µV
200µV
500µV
333µV
1000nA
800nA
700nA
: Partial change required, ×: Incompatible
Precautions for replacement
Since the resolution differs
between AnS series and L series
modules, it needs to be matched
using a sequence program, user
range settings, or the scaling
function. (Refer to Appendix 3.)
Since the resolution differs
between AnS series and L series
modules, it needs to be matched
using a sequence program, user
range settings, or the scaling
function. (Refer to Appendix 3.)
Consider replacement with several
L60DA4 modules.
3
- 12

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec-ans seriesMelsec-qnas series

Table of Contents