Mitsubishi Electric MELSEC L Series Manual page 103

Small type s intelligent function modules
Hide thumbs Also See for MELSEC L Series:
Table of Contents

Advertisement

4
ANALOG I/O MODULE REPLACEMENT
When the scaling function is used: -32768 to 32767
(External load resistance value: 1K to 1M)
(External load resistance value: 0 to 600)
Analog output range
Voltage
-10 to 10V
User range settings
0 to 20mA
Current
4 to 20mA
User range settings
Analog output range
Voltage
-10 to 10V
0 to 20mA
Current
4 to 20mA
Between the I/O terminal and programmable controller power supply: Photocoupler
Between I/O channels: Not insulated
Between external power supply and analog I/O channel: Transformer
Between the I/O terminal and programmable controller power supply: 500VACrms, for 1 minute
Between external power supply and analog I/O: 500VACrms, for 1 minute
Between the I/O terminal and programmable controller power supply: 500VDC, 10M or higher
(I/O assignment: intelligent 16 points)
R1.25-3 (Solderless terminals with an insulation sleeve cannot be used.)
L60AD2DA2
2 channels/module
-16384 to 16383
-10 to 10VDC
0 to 20mA
Digital input value
0 to 5V
0 to 12000
1 to 5V
-16000 to 16000
-12000 to 12000
0 to 12000
-12000 to 12000
Ambient temperature
25±5°C
0 to 5V
Within ±0.2%
(±10mV)
1 to 5V
Within ±0.2%
(±20mV)
Within ±0.2%
(±40µA)
80µs/channel
Available
16 points
18-point terminal block
2
0.3 to 0.75mm
24VDC +20%, -15%
Ripple, spike 500mVp-p or lower
0.12A
3.5A, 1000µs or less
0.17A
0.22kg
: Compatible,
Compatibility
Resolution
416µV
333µV
625µV
319µV
1666nA
1333nA
696nA
0 to 55°C
Within ±0.4%
(±20mV)
Within ±0.4%
(±40mV)
Within ±0.4%
(±80µA)
×
×
×
: Partial change required, ×: Incompatible
Precautions for replacement
Since the resolution differs
between AnS series and L series
modules, it needs to be matched
using a sequence program, user
range settings, or the scaling
function. (Refer to Appendix 3.)
The number of occupied I/O points
is changed to 16 points.
Wiring change is required.
Inrush current is greater.
4
- 24

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec-ans seriesMelsec-qnas series