5
HEATING-COOLING TEMPERATURE CONTROL MODULE/
L60TCTT4
–
*1
Calculate the accuracy in the following method.
(Accuracy) = (Indication accuracy) + (Cold junction temperature compensation accuracy)
(Example) Accuracy at the input range of 38, the operating ambient temperature of 35°C, and the temperature process
value (PV) of 300°C
{400.0-(-200.0)} [Full scale] × (±0.007)[±0.7%] + (±1.0°C) [Cold junction temperature compensation accuracy] = ±5.2°C
Specifications
L60TCTT4BW
U.R.D. Co., LTD.
CTL-12-S36-8
CTL-12-S36-10
CTL-12-S56-10
CTL-6-P(-H)
Full scale × (±1.0%)
3 to 255
: Compatible,
: Partial change required, ×: Incompatible
Compatibility
Precautions for replacement
5
- 24