ANALOG OUTPUT MODULE REPLACEMENT
When the scaling function is used: -32768 to 32767)
Voltage: -10 to 10VDC (External load resistance value: 1K to 1M)
Current: 0 to 20mA (External load resistance value: 0 to 600)
Analog output range
0 to 5V
1 to 5V
Voltage
-10 to 10V
User range settings
0 to 20mA
Current
4 to 20mA
User range settings
Ambient temperature 25±5°C: within ±0.1%
(voltage: ±10mV, current: ±20µA)
Ambient temperature 0 to 55°C: within ±0.3%
(voltage: ±30mV, current: ±60µA)
L60DA4
16-bit signed binary
(-20480 to 20479,
Digital value
Maximum resolution
250µV
0 to 20000
200µV
500µV
-20000 to 20000
333µV
1000nA
0 to 20000
800nA
-20000 to 20000
700nA
20µs/channel
4 channels/module
Up to 50000 times
Available
: Compatible,
: Partial change required, ×: Incompatible
Compatibility
Precautions for replacement
Since the resolution differs
between AnS series and L series
modules, it needs to be matched
using a sequence program, user
range settings, or the scaling
function. (Refer to Appendix 3.)
Since the resolution differs
between AnS series and L series
modules, it needs to be matched
using a sequence program, user
range settings, or the scaling
function. (Refer to Appendix 3.)
3
- 20