HEATING-COOLING TEMPERATURE CONTROL MODULE/TEMPERATURE
*1
Calculate the accuracy in the following method.
(Accuracy) = (Indication accuracy) + (Cold junction temperature compensation accuracy)
(Example) Accuracy at the input range of 38, the operating ambient temperature of 35°C, and the temperature process
value (PV) of 300°C
{400.0-(-200.0)} [Full scale] × (±0.007)[±0.7%] + (±1.0°C) [Cold junction temperature compensation accuracy] = ±5.2°C
5