Table 3-4 Typical Ups Efficiencies At Various Loads - Toshiba G9000 SERIES Installation And Operation Manual

480/480 v 100/160/225/300/500/750 kva
Hide thumbs Also See for G9000 SERIES:
Table of Contents

Advertisement

Rated Output kVA
Clearance Required
Sides: 0 in. (0 mm) if sidecars used, 1 in. (25 mm) if no
Enclosure
Audible Noise
Listings/Standards
ENERGY STAR® certified UPS, UL 1778; cUL; FCC
ISO 9001; ISO14001; ANSI C62.41 (IEEE 587 Cat. B)
Warranty
Emergency Power Off
MONITORING
Dry Contacts Included
RS232 Port
Intelligent Monitoring
(Optional)
Display
UNIT
100 kVA
160 kVA
225 kVA
300 kVA
500 kVA
750 kVA
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
100
160
Top: 20 in. (508 mm)
Front: 40 in. (1016 mm)
Rear: 0 in. (0 mm)
sidecars used.
70 dB @ 1 m
Class A-Article 47 – Part 15 B;
Yes, for Input and Output Signals
SNMP; MODBus RTU; MODBus TCP; BACNET; METASYS
LCD Touch Panel for Local Monitoring, Operation, and Control

Table 3-4 Typical UPS Efficiencies at Various Loads

20%
40%
92.5%
94.3%
94.7%
95.7%
94.9%
96.2%
94.4%
96.3%
94.8%
96.7%
95.5%
96.6%
225
300
Top: 23.6 in. (600 mm)
Front: 42.3 in. (1075 mm)
Rear: 0 in. (0 mm)
Sides: 0 in. (0 mm) if sidecars used, 1 in. (25 mm) if
no sidecars used.
NEMA 1
ENERGY STAR® certified UPS, UL 1778; cUL; IEC
62040-2 Cat. C3;
ISO 9001; ISO14001; ANSI C62.41 (IEEE 587 Cat. B)
3 Years Parts and Labor
Included
Included
% Full Load
60%
80%
95.0%
95.2%
96.2%
96.5%
96.5%
96.5%
96.9%
97.0%
97.0%
97.0%
97.0%
97.0%
500
750
73 dB @ 1 m
100%
95.8%
96.5%
96.5%
97.0%
97.0%
97.0%