Toshiba G9000 SERIES Installation And Operation Manual page 83

480/480 v 100/160/225/300/500/750 kva
Hide thumbs Also See for G9000 SERIES:
Table of Contents

Advertisement

Note 3
Code
Status message
indication
UA824
CB2 OPEN
52C OPEN
UA827
PROHIBITED
EMERGENCY
UA831
BYPASS SWITCH ON
UA833
52L OPEN
BATTERY
UA834
DEPLETED/AC OUT
STOPPED
TRANSFER
UA835
PROHIBITED
REMOTE BUTTON
UA860
ABNORMAL
LOCAL BUTTON
UA861
ABNORMAL
BALANCER
UA870
OVERLOAD
UA890
EXTERNAL ALARM
INPUT CIRCUIT
UF001
ABNORMAL
CONVERTER
UF002
OVERCURRENT
CONVERTER
UF003
ABNORMAL
UF011
CB1 ABNORMAL
UF052
CB1 ABNORMAL
CONVERTER
UF056
OVERCURRENT
INPUT CIRCUIT
UF059
ABNORMAL
UF102
DC OVERVOLTAGE
UF103
DC UNDERVOLTAGE
CHOPPER
UF108
OVERCURRENT
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Meaning
The battery circuit breaker (CB2) is open.
The interlock for the inverter output contactor
(52C) is active.
Emergency bypass switch has been turned on.
The load circuit breaker (52L) is turned off.
The battery voltage has reached the depleted
level.
The UPS could not transfer to the bypass
because the bypass source has an
abnormality.
Remote start or stop signal is being received
continuously for a considerable time.
Local start or stop signal is being received
continuously for a considerable time.
The UPS detected a neutral point voltage
unbalance.
External Alarm relay turned on.
The MMS input reference error signal exceeds
specifications.
Detection of MMS converter overcurrent.
Pre-charging circuit is not working properly.
Major discrepancy between reference signal
and actual state of contactor CB1.
Minor discrepancy between reference signal
and actual state of contactor CB1.
Detection of SMS converter overcurrent.
The SMS input reference error signal exceeds
specifications.
DC voltage surpasses the overvoltage level.
DC voltage dropped below the undervoltage
level.
Detection of DC overcurrent from backup
battery.
Guidance
Buzzer
Intermittent
TURN ON CB2
sound
Intermittent
sound
Intermittent
sound
Intermittent
sound
Intermittent
sound
Intermittent
sound
Intermittent
sound
Intermittent
sound
CALL SERVICE
Continuous
ENGINEER
sound
CALL SERVICE
Continuous
ENGINEER
sound
CALL SERVICE
Continuous
ENGINEER
sound
CALL SERVICE
Continuous
ENGINEER
sound
CALL SERVICE
Intermittent
ENGINEER
sound
CALL SERVICE
Intermittent
ENGINEER
sound
CALL SERVICE
Intermittent
ENGINEER
sound
CALL SERVICE
Continuous
ENGINEER
sound
CALL SERVICE
Continuous
ENGINEER
sound
CALL SERVICE
Continuous
ENGINEER
sound
Note 1
Note 2
External relay
Failure
contact
lamp
Alarm
Alarm
Alarm
Alarm
Major
End-of-
Lit on
Discharge
Alarm
Alarm
Alarm
Alarm
Overload
Alarm
Major
Lit on
Major
Lit on
Major
Lit on
Major
Lit on
Minor
Flicker
Minor
Flicker
Minor
Flicker
Major
Lit on
Major
Lit on
Major
Lit on