PARTS REPLACEMENT

A) Recommended Maintenance
Toshiba International Corporation recommends the UPS have regular preventative maintenance (PM)
visits to ensure optimum operation and longevity. Toshiba recommends two Major PM's per year, at six
month intervals.
A Major PM includes maintenance of the batteries and an offline inspection of the UPS. Contact Toshiba
International Corporation Service Department at 1-877-867-8773 for further details.
B) Battery
Battery lifetime may vary according to the frequency of use and the average ambient operating
temperature. The end of battery life is defined as the state of charge resulting in an ampere-hour
capacity less than, or equal to, 80% of nominal capacity.
Battery replacement is recommended if its capacity is within this percentage.
C) UPS Component Parts
UPS components have a defined life expectancy (Fans, Capacitors, Filters, etc.)
Contact Toshiba International Corporation or its authorized service representatives for a complete parts
replacement schedule. Recommended replacement time interval varies with operating environment.
Contact Toshiba International Corporation or its authorized service representatives for application
specific recommendations.
Cooling fans
Electrolytic Capacitors
AC filter Capacitors
Control Relays
Contactors
PCB
Control power supply
LCD
Fuses
Thermal relays
WARNING
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Table 7-1 Standard Replacement Parts List

Parts name
Any parts replacements (including modification) without authorized by
Toshiba could result in personal injuries, death or destruction of the UPS.
Life Expectancy
5 years
15 years
15 years
15 years
15 years
15 years
15 years
10 years
10 years
10 years