Toshiba G9000 SERIES Installation And Operation Manual page 95

480/480 v 100/160/225/300/500/750 kva
Hide thumbs Also See for G9000 SERIES:
Table of Contents

Advertisement

Installation Planning Guide for 300kVA UPS
Dimensions
(W x D x H)
Inches
51.2" x 32.7" x 80.7"*
* Height includes removable fan housing – Frame height is 78.7".
** 0" clearance for peripheral equipment, 1" clearance for walls.
Maximum Input Power Demand
Normal Mode (Recharge Mode)
kVA
PF
312 (336)
>0.99
Maximum Input Power Demand
kVA
PF
Amps (Max.)
300
1.0
361
Battery Capacity Required
for Full Load Output
kWB
311 @ 1.0 PF
*** Optimally Conservative Breaker Sizing. Contact Toshiba Factory Representative for Alternate Configurations.
Rated Output Power
kVA
PF
Amps
300
1.0
361
Important Notes:
1.
Maximum input current is limited to 106% of the full-load
input current.
2.
Output load conductors are to be installed in separate
conduit from input conductors.
3.
Control wires and power wires are to be installed in
separate conduits.
4.
Recommended AC input and output overcurrent protection
based on continuous full load current per NEC.
5.
Wiring shall comply with all applicable national and local
electrical codes.
6.
Grounding conductors to be sized per NEC Article 250-122.
Neutral conductors to be sized per NEC Article 310.15.
- Primary AC Input: 3φ, 3-wire + ground.
- Alternate AC Input: 3φ, 3-wire + ground.
- AC Output: 3φ, 3-wire + ground.
- DC Input: 2-wire (Positive/Negative) + ground.
7.
Nominal battery voltage based on the use of VRLA type
batteries (2.0 volts/cell nominal).
8.
Maximum battery discharge current based on lowest
permissible discharge voltage of 1.67 VPC.
9.
DC wires should be sized to allow not more than a 2-volt
drop at maximum discharge current.
10. Weights do not include batteries or other auxiliary
equipment external to the UPS.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Standard System: 480V Input, 480V Output
General Mechanical Information
Approximate Full-Load
Floor
Weight
Heat Rejection
Loading
2
Lbs.
Lbs./ft.
1230
189
Primary AC Input (480V 3-Phase / 3-Wire)
Suggested External
Overcurrent Protection
Amps
376 (404)
500 AT
Alternate (Bypass) AC Input (480V 3-Phase / 3-Wire)
Suggested External
Overcurrent Protection
Amps
500 AT
Battery Input (480VDC Nominal)
Discharge at Full
Suggested External
Load Output
Overcurrent Protection***
Amps DC
776
AC Output (480V 3-Phase / 3-Wire)
Suggested External
Overcurrent Protection
Amps
500 AT
Mechanical Clearance (Inches)from UPS
for Ventilation and Maintenance Access
Btu/Hr.
Top
31,659
23.6"
External Feeder Wire Size: Min. – Max. Per Phase
Amps
(2) x 250 kcmil - (2) x 300 kcmil
External Feeder Wire Size:
Min. – Max. Per Phase
AWG or kcmil at 75º C Temp. Rating
(2) x 250 kcmil - (2) x 300 kcmil
Amps
800 AT
(3) x 300 kcmil - (3) x 350 kcmil
External Feeder Wire Size:
Min. – Max. Per Phase
AWG or kcmil at 75º C Temp. Rating
(2) x 250 kcmil - (2) x 300 kcmil
11. Cable sizing calculations based on the following assumptions:
- Minimum size is smallest size based on ampacity at 30 °C.
- Maximum size cable is based on cable bend radius
limitations at the UPS terminals.
- Not more than 3 current-carrying conductors installed in
conduit in ambient temperature of 30 °C.
- Temperature rating of copper conductors/terminals: 75 °C in
conduit.
- Reference: 2005 NEC Handbook, Table 310.16.
NOTE: Consult latest edition of applicable
national and local codes for possible
variations.
12. Ratings of wires and overcurrent devices are suggested
minimums. Consult with a registered Professional Engineer
within your local area for proper size selections.
TOSHIBA
INTERNATIONAL CORPORATION
13131 West Little York Road
Houston, TX 77041
Telephone: (800) 231-1412
Fax: (713) 896-5212
Front
Bottom
Sides**
42.3"
0"
0"
AWG or kcmil at 75º C Temp. Rating
External Feeder Wire Size:
AWG or kcmil at 75º C Temp. Rating
Back
0"