Table 4-2 External Output Functions; Figure 4-21 External Signal Output Terminal Block (With Default Settings) - Toshiba G9000 SERIES Installation And Operation Manual

480/480 v 100/160/225/300/500/750 kva
Hide thumbs Also See for G9000 SERIES:
Table of Contents

Advertisement

Figure 4-21 External Signal Output Terminal Block (with default settings)

These contacts can be programmed to provide any of the functions shown in Table 2.2. The default
programmed values are indicated with an asterisk (*).
Code
Function
0
NONE
1 *
TOTAL ALARM
2 *
MINOR FAULT
3
ALARM
4
AC INPUT ABNORMAL
5
BYPASS ABNORMAL
6
BATTERY ABNORMAL
7
BATTERY LOW VOL.1
8 *
BATTERY LOW VOL.2
9
BATTERY DEPLETION
UPS
10 *
OVERLOAD
11
OVERLOAD PREALARM
12
FAULT GROUP 1
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Table 4-2 External Output Functions

Summary alarm; activated when any minor, major, fault or alarm has occurred
with the system. This is the default setting on OUT8.
Activated when a minor fault has occurred with the system.
Activated when an alarm has occurred with the system.
Activated when the input voltage or frequency is abnormal.
Activated when the bypass voltage or frequency is abnormal.
Activated when the battery is abnormal.
Activated when the battery voltage drops below Discharge Warning Voltage
Level 1 during inverter operation. This level is set in the TEST MENU by an
Authorized Toshiba Service Provider.
Activated when the battery voltage drops below Discharge Warning Voltage
Level 2 during inverter operation. This level is set in the TEST MENU by an
Authorized Toshiba Service Provider. This is the default setting for OUT5.
Activated when the battery voltage drops below discharge end voltage level
during inverter operation.
Activated when an overload of 105% or more had occurred to the system.
This is the default setting on OUT6.
Activated when the load goes over 100%. This level is adjustable by an
Authorized Toshiba Service Provider.
Activated when the preset group of alarms (Fault Group 1) all occur to the
system at once. These groups are set in the TEST MENU by an Authorized
Toshiba Service Provider.
Description

Advertisement

Table of Contents
loading